2-Channel, True RMS, 0 to 1V AC, DataView Software.
2-Channel, True RMS, 0 to 1V AC, DataView Software.
Discontinued!
This product has been discontinued and is no longer available.
This is the direct replacement:
The Simple Logger® II Model L102 is a two channel recording device powered by two alkaline batteries. Line tracking is performed such that 64 samples over one line cycle are taken. Frequency tracking is performed over the range of ±2Hz around the nominal line frequency (50 or 60Hz). Harmonic measurements are calculated from these 64 samples (Harmonics are only available from the Simple Logger® II Control Panel within the DataView® software).
The Simple Logger® II records TRMS at a rate of up to eight times per second. The measurement process is performed no more than eight times per second. TRMS calculations are performed on a single line cycle. This means that the input(s) are ignored between measurement intervals. The main advantage of the logger is its ability to perform a variety of recording tasks with easy and intuitive setup from a computer using DataView® software.
Analog information on the input is sampled and converted to a digital signal. This digital signal is processed and stored along with scale and time information. An optically isolated Universal Serial Bus (USB) port provides for the transfer of data from the instrument's internal memory to the computer for analysis.
Simple Logger II Model L102 | |
Electrical | |
Channels | Two |
Input Connection | One BNC connector per channel |
Measurement Range | 0 to 1V |
Resolution | 0.1mV |
Accuracy | (50/60Hz) 0 to 10mV: unspecified 10 to 50mV: ±(0.5% of Reading + 1mV) 50 to 1000mV: ±(0.5% of Reading + 0.5mV) |
Sample Rate | 64 samples/cycle |
Storage Rate | Programmable from 125ms to 1 day |
Storage Modes | Start/Stop, FIFO and Extended Recording Mode (XRM™) |
Recording Length | 15 minutes to 8 weeks, programmable using DataView |
Memory | 240,000 measurements (512KB) - The recorded data is stored in non-volatile memory and will be retained even if the battery is low or removed. |
Communication | USB 2.0 optically isolated |
Power Source | 2 x 1.5V AA-cell alkaline batteries |
Battery Life | 100 hours to >45 days (dependent on sample rate and recording length) |
Mechanical | |
Dimensions | 5.38 x 2.75 x 1.28" (136 x 70 x 32mm) |
Max Conductor Size | Current probe dependent |
Weight (with battery) | 6.4 oz (181 grams) |
Case | UL94-V0 |
Vibration | IEC 68-2-6 (1.5mm, 10 to 55Hz) |
Shock | IEC 68-2-27 (30G) |
Drop | IEC 68-2-32 (1m) |
Simple Logger II Model L102 | |
Electrical | |
Channels | Two |
Input Connection | One BNC connector per channel |
Measurement Range | 0 to 1V |
Resolution | 0.1mV |
Accuracy | (50/60Hz) 0 to 10mV: unspecified 10 to 50mV: ±(0.5% of Reading + 1mV) 50 to 1000mV: ±(0.5% of Reading + 0.5mV) |
Sample Rate | 64 samples/cycle |
Storage Rate | Programmable from 125ms to 1 day |
Storage Modes | Start/Stop, FIFO and Extended Recording Mode (XRM™) |
Recording Length | 15 minutes to 8 weeks, programmable using DataView |
Memory | 240,000 measurements (512KB) - The recorded data is stored in non-volatile memory and will be retained even if the battery is low or removed. |
Communication | USB 2.0 optically isolated |
Power Source | 2 x 1.5V AA-cell alkaline batteries |
Battery Life | 100 hours to >45 days (dependent on sample rate and recording length) |
Mechanical | |
Dimensions | 5.38 x 2.75 x 1.28" (136 x 70 x 32mm) |
Max Conductor Size | Current probe dependent |
Weight (with battery) | 6.4 oz (181 grams) |
Case | UL94-V0 |
Vibration | IEC 68-2-6 (1.5mm, 10 to 55Hz) |
Shock | IEC 68-2-27 (30G) |
Drop | IEC 68-2-32 (1m) |