Featuring automatic or manual setups and preprogrammed monitoring modes, with 4 differential 50/60hz, AC/DC voltage channels and 4 AC/DC current channels with flex probe power supply.
Our rentals come fully calibrated to traceable standards. Have your own instrument? We also offer calibration services for this model (CERTIWM3).
Featuring automatic or manual setups and preprogrammed monitoring modes, with 4 differential 50/60hz, AC/DC voltage channels and 4 AC/DC current channels with flex probe power supply.
Our rentals come fully calibrated to traceable standards. Have your own instrument? We also offer calibration services for this model (CERTIWM3).
The Dranetz HDPQ Guide and HDPQ Guide SP are your all-in-one power monitoring tools that provide you with everything needed to get the job done. Both the HDPQ Guide and Guide SP series offer the exact same measurement features, but in different enclosures that can meet the needs of a wide variety of applications and work environments.
Features
Applications
| Paramètres mesurés | |
| Entrées de tension différentielle (4) | 1 à 1 000 Vrms, c.a./c.c.; ±0,1 % lecture, <40 V ±0,05 % FS; 512 échantillons/cycle; résolution CAN à 16 bits |
| Measured Parameters | |
| Differential Voltage Inputs (4) | 1-1000Vrms, AC/DC; ±0.1% rdg., <40V ±0.05% FS; 512 samples/cycle; 16-bit ADC resolution |
| Current Inputs with CTs (4) | 0.1-6000Arms CT-Dependent, AC/DC; ±0.1% rdg. ±0.05% FS; 512 samples/cycle; 16-bit ADC resolution |
| Frequency Range | 16 to 25Hz, 42.5 to 69Hz, ±0.01Hz |
| Calculated Parameters | |
| Vthd | 0 to 100%, ±5% for V ≥ 1% Vnom |
| V Ind Harm | DC, 2 to 127, ±5% for V ≥ 1% Vnom |
| Ithd | 0 to 100%, ±5% for V ≥ 1% Vnom |
| I Ind Harm | DC, 2 to 63, ±5% for V ≥ 1% Vnom |
| Pst | 10 minutes: 0.2 to 10, ±0.05 at Pst=1 |
| Plt | 2 hours: 0.2 to 10, ±0.05 at Pst=1 |
| General Specifications | |
| Memory Size | 4GB |
| Display (HDPQ Guide) | 7in (17.78cm) WVGA color graphic, icon-based touch LCD, LED backlit |
| Power Supply (HDPQ Guide) | AC Adapter, 90 to 264VAC 50/60Hz |
| Dimensions (HDPQ Guide) | 10 x 2.75 x 8in (25.4 x 7.0 x 20.3cm) |
| Weight (HDPQ Guide) | 4.2lbs (1.9kg) |
| Power Supply (HDPQ Guide SP) | 90 to 600VAC/500VDC (50/60Hz); powered by the phase being measured or other source |
| Dimensions (HDPQ Guide SP) | 11 x 2.5 x 6.5in (27.9 x 6.4 x 16.5cm) |
| Weight (HDPQ Guide SP) | 3.8lbs (1.72kg) |
| Paramètres mesurés | |
| Entrées de tension différentielle (4) | 1 à 1 000 Vrms, c.a./c.c.; ±0,1 % lecture, <40 V ±0,05 % FS; 512 échantillons/cycle; résolution CAN à 16 bits |
| Measured Parameters | |
| Differential Voltage Inputs (4) | 1-1000Vrms, AC/DC; ±0.1% rdg., <40V ±0.05% FS; 512 samples/cycle; 16-bit ADC resolution |
| Current Inputs with CTs (4) | 0.1-6000Arms CT-Dependent, AC/DC; ±0.1% rdg. ±0.05% FS; 512 samples/cycle; 16-bit ADC resolution |
| Frequency Range | 16 to 25Hz, 42.5 to 69Hz, ±0.01Hz |
| Calculated Parameters | |
| Vthd | 0 to 100%, ±5% for V ≥ 1% Vnom |
| V Ind Harm | DC, 2 to 127, ±5% for V ≥ 1% Vnom |
| Ithd | 0 to 100%, ±5% for V ≥ 1% Vnom |
| I Ind Harm | DC, 2 to 63, ±5% for V ≥ 1% Vnom |
| Pst | 10 minutes: 0.2 to 10, ±0.05 at Pst=1 |
| Plt | 2 hours: 0.2 to 10, ±0.05 at Pst=1 |
| General Specifications | |
| Memory Size | 4GB |
| Display (HDPQ Guide) | 7in (17.78cm) WVGA color graphic, icon-based touch LCD, LED backlit |
| Power Supply (HDPQ Guide) | AC Adapter, 90 to 264VAC 50/60Hz |
| Dimensions (HDPQ Guide) | 10 x 2.75 x 8in (25.4 x 7.0 x 20.3cm) |
| Weight (HDPQ Guide) | 4.2lbs (1.9kg) |
| Power Supply (HDPQ Guide SP) | 90 to 600VAC/500VDC (50/60Hz); powered by the phase being measured or other source |
| Dimensions (HDPQ Guide SP) | 11 x 2.5 x 6.5in (27.9 x 6.4 x 16.5cm) |
| Weight (HDPQ Guide SP) | 3.8lbs (1.72kg) |